Wire Sizing at a Glance
Wire must carry the full load current without overheating. This calculator applies the NEC Table 310.16 ampacity values (60°C column) and the 125% continuous-load rule to recommend a conductor size. A 20 A continuous load needs wire rated for 25 A — that is 12 AWG copper minimum, with 10 AWG the safer choice.
How Wire Sizing Works
1) Determine the load current in amps. 2) If the load runs 3+ hours continuously, multiply by 1.25 (NEC 210.19). 3) Select the smallest wire whose ampacity meets or exceeds that value. 4) Apply derating for high ambient temperature or multiple conductors in one conduit — both reduce a wire’s safe current.
Copper vs Aluminum
Copper carries more current per size and is the default for branch circuits. Aluminum is cheaper for large feeders but needs larger sizes (e.g., where 6 AWG copper suffices, aluminum needs 4 AWG) and special termination practices to prevent oxidation. Never mix copper and aluminum in one terminal without rated connectors.