Correct conductor size per NEC 310.16 — copper or aluminum.

Calculator Input

LIVE  Live calculation — type and watch the result.

Full-load current of the circuit.

Recommended Wire

—
Enter values to calculate

Details

—

Wire Sizing at a Glance

Wire must carry the full load current without overheating. This calculator applies the NEC Table 310.16 ampacity values (60°C column) and the 125% continuous-load rule to recommend a conductor size. A 20 A continuous load needs wire rated for 25 A — that is 12 AWG copper minimum, with 10 AWG the safer choice.

How Wire Sizing Works

1) Determine the load current in amps. 2) If the load runs 3+ hours continuously, multiply by 1.25 (NEC 210.19). 3) Select the smallest wire whose ampacity meets or exceeds that value. 4) Apply derating for high ambient temperature or multiple conductors in one conduit — both reduce a wire’s safe current.

Copper vs Aluminum

Copper carries more current per size and is the default for branch circuits. Aluminum is cheaper for large feeders but needs larger sizes (e.g., where 6 AWG copper suffices, aluminum needs 4 AWG) and special termination practices to prevent oxidation. Never mix copper and aluminum in one terminal without rated connectors.

Frequently Asked Questions

What wire for a 30 A circuit?
10 AWG copper (30 A at 60°C). For continuous loads, 8 AWG is required after the 125% rule (37.5 A).
Can I use 14 AWG on a 20 A breaker?
No — 14 AWG is rated 20 A at 60°C but NEC 240.4(D) limits it to 15 A protection. Use 12 AWG for 20 A circuits.
Does wire length matter?
Yes — long runs cause voltage drop. Above ~30 m, upsize one gauge to keep drop under 3% for branch circuits.