⚡ VoltEdge

Breaker Size Calculator

Correct protection per NEC 210.19 and 430.52.

Calculator Input

LIVE  Live calculation — type and watch the result.

Full-load amps from calculation or nameplate.

Recommended Breaker

—
Enter values to calculate

Details

—

Breaker Sizing at a Glance

A breaker’s job is to protect the wire, not the appliance. Size it from the load current: continuous loads (running 3+ hours) need 125% sizing per NEC 210.19, motors follow NEC 430.52 (up to 250%), and non-continuous loads use 100%. An 18 A continuous load needs 22.5 A → a 25 A breaker.

The Sizing Rules

Breaker Protects Wire — Always Check Both

Selecting a 32 A breaker for a 25 A load is only half the job: the wire must also be rated for 32 A. A breaker larger than the wire’s ampacity is a fire hazard the breaker itself will never catch. Size the wire first, then the breaker — never the reverse.

Frequently Asked Questions

What breaker for a 20 A continuous load?
20 × 1.25 = 25 A → use a 25 A breaker with wire rated ≥25 A (4 mm² / 10 AWG).
Can I use a bigger breaker to stop tripping?
No — upsizing the breaker without upsizing the wire is dangerous. Find why it trips: overload, short circuit, or ground fault.
What breaker for a 7.5 kW motor at 400 V?
FLA ≈ 15.2 A. Per NEC 430.52, up to 38 A instantaneous-trip is permitted; a 32 A motor-rated (type D) breaker with a 15–16 A overload relay is standard.