Free A4 PDF — kW to amps tables, motor FLA and breaker quick reference.
How to Read This Chart
Find your kilowatt rating in the left column, then read across to your circuit type. Values assume standard voltages; for exact sizing, use the calculator with your measured voltage and nameplate power factor.
kW to Amps — Common Ratings
| kW | DC / 1-ph 230V | 1-ph 230V PF 0.8 | 3-ph 400V PF 0.85 | 3-ph 415V PF 0.85 |
|---|---|---|---|---|
| 0.5 | 2.2 A | 2.7 A | 0.8 A | 0.8 A |
| 1 | 4.3 A | 5.4 A | 1.7 A | 1.6 A |
| 1.5 | 6.5 A | 8.2 A | 2.5 A | 2.5 A |
| 2 | 8.7 A | 10.9 A | 3.4 A | 3.3 A |
| 3 | 13.0 A | 16.3 A | 5.1 A | 4.9 A |
| 5 | 21.7 A | 27.2 A | 8.5 A | 8.2 A |
| 7.5 | 32.6 A | 40.8 A | 12.7 A | 12.3 A |
| 10 | 43.5 A | 54.3 A | 17.0 A | 16.4 A |
| 15 | 65.2 A | 81.5 A | 25.5 A | 24.6 A |
| 20 | 87.0 A | 108.7 A | 34.0 A | 32.7 A |
| 30 | 130.4 A | 163.0 A | 50.9 A | 49.1 A |
| 50 | 217.4 A | 271.7 A | 84.9 A | 81.8 A |
| 75 | 326.1 A | 407.6 A | 127.4 A | 122.8 A |
| 100 | 434.8 A | 543.5 A | 169.8 A | 163.7 A |
Motor Full-Load Current Reference
Typical full-load amps for standard 400 V three-phase motors at 0.85 PF — verify against the motor nameplate:
| Motor kW | FLA (A) | Suggested Breaker |
|---|---|---|
| 1.1 | 2.7 | 6 A |
| 2.2 | 5.0 | 10 A |
| 4 | 8.8 | 16 A |
| 7.5 | 15.2 | 25 A |
| 15 | 29.5 | 40 A |
| 22 | 42.5 | 63 A |
| 37 | 69.8 | 100 A |
| 55 | 102 | 125 A |
Breaker suggestions assume motor-rated (type D) breakers and must be confirmed against your local electrical code.