kW to Amps 3 Phase Calculator

Built for industrial and commercial work — enter the load, the line voltage, and power factor to get the per-phase current.

Calculator Input

LIVE  Live calculation — type and watch the result.

The total three-phase load rating from the equipment nameplate.
Measure between any two phases: 400, 415 or 480 V are the common ones.
Motors typically run 0.75–0.9. Use the nameplate value when available.

Conversion Result

—
Enter values to calculate

Formula Used

—

How Three-Phase Conversion Works

1

Enter the total power

The full three-phase kW rating of the motor or equipment.

2

Enter the line-to-line voltage

Voltage between phases — not phase to neutral.

3

Set the power factor

Motors are inductive, so 0.85 is a realistic starting point.

4

Read the per-phase current

The result is the amps in each of the three conductors.

Three-Phase Formulas

Three-phase: I = (kW × 1000) ÷ (√3 × V × PF)

The √3 (about 1.732) comes from the geometry of three phases spaced 120° apart — it scales the voltage correctly when all three conductors share the power.

Line-to-line voltage: V = voltage measured between any two phases

Always use the phase-to-phase figure (400 V, not 230 V) in the three-phase formula. Mixing in the phase-to-neutral voltage is the most common mistake.

Reverse (amps → kW): kW = (I × √3 × V × PF) ÷ 1000

Multiply the per-phase amps by √3, the line voltage and the power factor, then divide by 1000.

What Three-Phase Power Actually Is

Three-phase power is three AC voltages, each peaking one-third of a cycle after the previous one, sharing the work across three wires. The three waveforms are spaced 120° apart, which means that at every instant at least one phase is delivering near-peak power. The total power flow stays nearly constant instead of pulsing to zero twice per cycle the way single-phase does — and that constant flow is why three-phase motors run smoother, quieter, and with far less vibration than single-phase motors of the same size.

A generator with three coil sets spaced 120° around its rotor produces the three phases naturally, and the grid carries them on three conductors. The calculator result is the current in each of those conductors — identical in all three for a balanced load.

Star and delta in one paragraph

Equipment connects to the three phases in one of two shapes: star (Y), where one end of each phase coil meets at a common neutral point — this gives you both voltages at once, 230 V phase-to-neutral and 400 V phase-to-phase; or delta (Δ), where the coils form a triangle with no neutral, the classic setup for heavy motors. Many motors carry both markings on the nameplate (e.g. Δ 400 V / Y 690 V) and the installer picks the connection to match the supply; the kW-to-amps math is the same either way as long as you enter the correct line-to-line voltage.

Why √3? The Factor Explained Plainly

√3 (≈1.732) is the geometric price of splitting power three ways at 120° — it converts the line-to-line voltage into the true per-phase basis the power equation needs. Here is the intuition: because the three waveforms overlap instead of lining up, you cannot just take single-phase math and divide by three, nor multiply by three — the vector sum of two phases 120° apart lands at √3 times one phase, not 2 times. The formula therefore multiplies the line voltage by √3 to account for how the phases combine.

Sanity-check it against voltages you know: 230 V × √3 = 398.4 V — exactly why a 230 V phase-to-neutral system measures 400 V phase-to-phase.

Line-to-Line vs Line-to-Neutral Voltage

The three-phase formula always wants the voltage measured between two phases (400 V) — never the phase-to-neutral voltage (230 V). This is the single most common three-phase mistake, and it is a dangerous one: feeding 230 V into the formula understates the current by a factor of √3, so the cable and breaker get sized for only about 58% of the real current — roughly 42% too small. On a motor circuit, that means a breaker that trips constantly at best, or cable running hot at worst.

Measure between any two of the three phase conductors with your meter set to AC volts — L1–L2, L2–L3, or L1–L3 should all read about the same. If you only have the line-to-neutral figure (say 230 V from a nameplate), multiply it by √3 to get the line-to-line value (400 V) before it goes anywhere near the formula. And if the nameplate lists something like 400 V Δ, that 400 V is already line-to-line: enter it directly.

Where Three-Phase Power Is Used

Three-phase is the standard for industrial motors, commercial HVAC, large pumps, compressors, and factory machinery. Typical supply levels are 400 V in Europe and much of Asia, 415 V in the UK and India, and 480 V in North American industry.

For the same kilowatt load, three-phase draws far less current per conductor than single-phase — power divided three ways. A 7.5 kW motor at 400 V with PF 0.85 draws (7.5 × 1000) ÷ (1.732 × 400 × 0.85) = 12.74 A per phase. That is why factories use three-phase: thinner cables, smaller breakers, and smoother-running motors.

The savings compound across a whole installation. Compare a 15 kW load: on 230 V single-phase at PF 0.85 it pulls about 76.73 A through one chunky conductor; on 400 V three-phase at the same power factor it pulls 25.47 A per phase through three modest ones. Less copper, smaller breakers, smaller switchgear — and the motors themselves are simpler, since three-phase motors need no starting capacitors or centrifugal switches. You will also find three-phase feeding elevators, commercial kitchens, welders, large UPS systems, and data-center power distribution. US commercial buildings often run 208 V three-phase; heavy industry uses 480 V.

Amps per Kilowatt: Quick Reference

At 400 V three-phase, 1 kW is only 1.44 A per phase — compare that with 4.35 A on 230 V single-phase. Reference table for the standard industrial voltages, at PF 1.0 and at a realistic motor PF of 0.85:

Line voltageAmps per 1 kW (PF 1.0)Amps per 1 kW (PF 0.85)
208 V2.78 A3.27 A
400 V1.44 A1.70 A
415 V1.39 A1.64 A
480 V1.20 A1.42 A

Two habits make this table fast to use: multiply by the kilowatt rating (a 22 kW pump at 400 V, PF 0.85, is 22 × 1.698 = 37.36 A), and remember that dropping the power factor from 1.0 to 0.85 lifts every figure by about 18%. For rough cable sizing in your head, 400 V three-phase at motor power factors works out to roughly 1.7 A per kW — close enough to sanity-check a quote or a nameplate.

Worked Examples

Example 1 — 15 kW workshop motor. A 15 kW three-phase motor on a 400 V supply, nameplate PF 0.85. I = (15 × 1000) ÷ (1.732 × 400 × 0.85) = 25.47 A per phase. The contactor, overload relay, and cable are all selected against 25.47 A — and the overload relay gets set just above it, not at some rounded-up guess.

Example 2 — 30 kW commercial load. A 30 kW rooftop HVAC package on 480 V three-phase, PF 0.9. I = (30 × 1000) ÷ (1.732 × 480 × 0.9) = 40.09 A per phase. Note how little current 30 kW needs at 480 V three-phase — the same power on 230 V single-phase would be over 150 A.

Example 3 — 22 kW pump. A 22 kW borehole pump on 415 V three-phase (common in the UK, India, and Australia), PF 0.88. I = (22 × 1000) ÷ (1.732 × 415 × 0.88) = 34.78 A per phase. If the nameplate PF were missing, 0.85 is the safe assumption, giving 36.00 A — barely a breaker size of difference.

Common Mistakes and Safety

Mistake number one is the voltage: line-to-neutral (230 V) in the formula instead of line-to-line (400 V) — it understates current by √3 and undersizes everything downstream. Close behind: forgetting the power factor entirely (motors are never PF 1.0), and the folk formula of “dividing by 3” instead of multiplying by √3, which has no basis in the physics and gives a wrong answer with false confidence.

On safety, be blunt with yourself: three-phase means higher voltages, higher fault currents, and arc-flash energy that can be lethal. Lock out and tag out before touching anything, prove dead on all three phases (not just one), and never work live. Three-phase installation and fault-finding are licensed-electrician territory everywhere — this page covers the arithmetic so you can check a quote or size a preliminary design, not so you can wire a panel.

Frequently Asked Questions

What is the three-phase kW to amps formula?
I = (kW × 1000) ÷ (√3 × V × PF), where V is the line-to-line voltage and √3 ≈ 1.732.
Should I use line-to-line or line-to-neutral voltage?
Line-to-line — measured between two phases. The √3 factor already accounts for the phase geometry, so using the 230 V neutral figure would understate the current.
Why does three-phase use less current per kW?
The power is split across three conductors instead of one, so each conductor carries roughly a third of the single-phase current for the same load.
What power factor do 3-phase motors have?
Usually 0.75–0.9 at full load, dropping when the motor is lightly loaded. The nameplate often lists it — use that figure when you have it.
Can this calculate breaker size?
It gives you the running current, which is the starting point. Breakers are then sized to code rules with the appropriate safety margins — check your local wiring regulations.
How many amps is 15 kW three-phase at 400 V?
25.47 A per phase at PF 0.85: (15 × 1000) ÷ (1.732 × 400 × 0.85) = 25.47. At unity power factor it would be 21.65 A.
Can I run a three-phase motor on a single-phase supply?
Not directly. A variable-frequency drive (VFD) or rotary phase converter can do it, but expect derating and extra cost — and the input current on the single-phase side will be much higher than the motor’s per-phase rating.