kW to Amps at 440V 3-Phase Calculator

Locked to 440 V three-phase — the industrial workhorse across India, Pakistan, and much of Asia.

Calculator Input

LIVE  Live calculation — type and watch the result.

The three-phase load rating from the equipment nameplate.
Fixed at 440 V line-to-line, the common Asian industrial supply.
Motors typically run 0.75–0.9. Use the nameplate value when available.

Conversion Result

—
Enter values to calculate

Formula Used

—

440 V 3-Phase Systems at a Glance

440 volts three-phase is the standard industrial supply across India, Pakistan, Bangladesh, and much of Southeast Asia — feeding factory motors, tube wells, commercial pumps, and workshop machinery. It is the voltage behind most of the region’s manufacturing and agricultural pumping.

At PF 1.0, 1 kW at 440 V 3-phase ≈ 1.31 A per phase. So a 10 kW load draws about 13.12 A per phase at unity PF — modest currents that keep cable sizes reasonable. Formula: I = (kW × 1000) ÷ (1.732 × 440 × PF).

Where 440 V Three-Phase Is Used

The 440 V three-phase supply is the backbone of industry across South Asia and parts of Southeast Asia. Factories run their lathes, compressors, and conveyor motors on it; workshops power welders and heavy machinery from it; and across the agricultural belts of India and Pakistan, tube-well pumps that lift groundwater for irrigation run for hours each day on 440 V three-phase. Commercial buildings use it for central air-conditioning plants, elevators, and large water pumps, while the 220–240 V single-phase tapped between one phase and neutral feeds the lighting and office loads.

It exists at this voltage for the same reason three-phase exists at all: efficiency at scale. A three-phase motor is simpler, cheaper, and more rugged than a single-phase motor of the same power, and splitting the load across three conductors keeps the per-phase current low — a 10 kW motor draws only about 13.12 A per phase at unity power factor, so the feeder cables stay modest even for serious machinery. The calculator above is locked to 440 V line-to-line with a typical motor power factor of 0.85, which matches the nameplate reality of most industrial motors in the region.

The 440 V Three-Phase Formula

On a three-phase system, power is shared across three conductors, so the single-phase equation gains one more divisor: the square root of 3 (about 1.732). That constant comes from the 120-degree spacing between the three voltage waveforms — it is what converts the line-to-line voltage into the equivalent per-phase figure.

440 V three-phase:  I = (kW × 1000) ÷ (√3 × 440 × PF)

The voltage in this formula is the line-to-line voltage: 440 V measured between any two of the three phase conductors. The voltage from any single phase to neutral is lower — 440 ÷ √3 = 254 V — which is why the same supply can feed both 440 V three-phase motors and 220–254 V single-phase equipment from a four-wire (three phases plus neutral) connection.

Amps per Kilowatt and Common Motor Sizes

The first table gives the per-phase current for each kilowatt of load at unity power factor and at a typical motor power factor of 0.85. The second translates common motor horsepower ratings into amps — motors in this region are usually sold by horsepower, so this is the table most workshop electricians reach for.

LoadAmps per phase (PF 1.0)Amps per phase (PF 0.85)
1 kW1.31 A1.54 A
5 kW6.56 A7.72 A
10 kW13.12 A15.44 A
15 kW19.68 A23.16 A
25 kW32.80 A38.59 A
Motor size≈ kW (shaft)Amps per phase (PF 0.85)
5 HP3.73 kW5.76 A
10 HP7.46 kW11.52 A
15 HP11.19 kW17.27 A
20 HP14.92 kW23.03 A

One caution with the motor table: horsepower is shaft (output) power, while the formula works on electrical (input) power. A real motor is not 100% efficient — typically 85–92% — so its actual full-load current runs a little higher than the table shows. The nameplate full-load amps (FLA) is always the authority for sizing starters, overloads, and cable; use the formula for quick checks and planning, then confirm against the plate.

Worked Examples

A 10 HP tube-well motor

Ten horsepower is 7.46 kW of shaft power. At PF 0.85: I = (7.46 × 1000) ÷ (1.732 × 440 × 0.85) = 7460 ÷ 647.70 = 11.52 A per phase. The motor starter and overload relay are set around this figure (plus the usual service margin), and the feeder cable is chosen for it.

A 25 kW air compressor

I = (25 × 1000) ÷ (1.732 × 440 × 0.85) = 25000 ÷ 647.70 = 38.59 A per phase. This is a substantial feeder — typically 16 mm² copper or the aluminium equivalent — protected by a 50 A breaker or MCCB with the overload relay tuned to the motor’s actual FLA.

A 3 kW pump at PF 0.8

Smaller pumps often run at a lower power factor: I = (3 × 1000) ÷ (1.732 × 440 × 0.8) = 3000 ÷ 609.66 = 4.92 A per phase. Light enough for a small DOL (direct-on-line) starter with a contactor and overload, which is how most sub-5 HP installations are wired.

Step-by-Step Calculation

1

Read the nameplate kW

Take the three-phase load rating — for motors, convert HP to kW (1 HP = 0.746 kW) if only horsepower is given.

2

Confirm 440 V line-to-line

Verify with a meter across two phases; do not use the 254 V phase-to-neutral figure in this formula.

3

Pick the power factor

Use the nameplate PF when printed; otherwise 0.85 is a sound default for induction motors.

4

Divide

Compute (kW × 1000) ÷ (1.732 × 440 × PF) to get amps per phase.

Star-Delta Starters in Brief

A large motor started direct-on-line can pull five to seven times its running current for a few seconds — enough to dim the lights, stress the windings, and trip breakers. The star-delta starter is the classic answer on 440 V systems: it first connects the motor windings in star, so each winding sees only 254 V (440 ÷ √3) and the starting current drops to about a third; once the motor is near full speed, contactors switch the windings to delta for normal 440 V running. It costs little more than a couple of extra contactors and a timer, which is why it remains the default starting method for motors above roughly 5–7.5 HP across South Asian industry. Size the starter and its overload relay from the motor’s nameplate full-load amps, not from a textbook estimate.

Common Mistakes to Avoid

Safety Note

440 V three-phase is firmly in lethal territory and carries far more fault energy than a household supply. Only a qualified electrician should open panels, terminate feeders, or set starters and overloads. Always follow lockout-tagout: isolate the circuit, lock the isolator in the off position, tag it, and test for dead on all three phases before touching anything. Verify starter settings and protective devices against the motor nameplate and your local electrical code — this page is an educational reference, not a substitute for that professional sign-off.

Frequently Asked Questions

1 kW at 440 V 3-phase — how many amps is that?
About 1.31 amps per phase at power factor 1.0, or roughly 1.54 A at PF 0.85.
What current does a 10 HP motor draw at 440 V?
10 HP is 7.46 kW. At PF 0.85 and 440 V 3-phase, that is about 11.52 A per phase.
Is 440 V line-to-line or line-to-neutral?
Line-to-line. The phase-to-neutral voltage on these systems is 254 V (440 ÷ √3).
Why is 440 V used instead of 400 V in some countries?
Historical grid standards. The math is identical — only the voltage figure in the formula changes.
Should I use 440 V or 415 V in the formula?
Use whichever your supply actually delivers — a 10 kW load at PF 0.85 draws 16.37 A at 415 V but 15.44 A at 440 V. Measure line-to-line at the equipment if you are unsure.
What is a star-delta starter for?
It starts large motors in star (each winding sees 254 V) to cut the inrush current to about a third, then switches to delta for normal 440 V running once the motor is up to speed.