⚡ VoltEdge

kW to Amps at 400V Calculator

Locked to 400 V — the European three-phase standard (400Y/230 V).

Calculator Input

LIVE  Live calculation — type and watch the result.

EU industrial motors and machinery are the typical 400 V loads.
Fixed at 400 V line-to-line, the common IEC industrial supply.
Motors typically run 0.75–0.9. Use the nameplate value when available.

Conversion Result

—
Enter values to calculate

Formula Used

—

400 V Three-Phase at a Glance

400 volts three-phase is the backbone of European industry. Under IEC 60038, the standard EU service is 400Y/230 V: 400 V between phases for machinery and 230 V phase-to-neutral for lighting and small loads. From German factories to French workshops, three-phase motors across Europe run on 400 V.

At PF 0.85, 1 kW at 400 V three-phase ≈ 1.70 A. A 22 kW industrial motor — an extremely common size — draws roughly 37.4 A, which is why 40 A breakers and 10 mm² cable are standard for this motor class. Formula: I = (kW × 1000) ÷ (1.732 × 400 × PF).

Where 400 V Three-Phase Is Used

The 400Y/230 V system is harmonized across the EU, the UK (as 400 V), and much of Africa, the Middle East, and Asia. Industrial estates receive 400 V three-phase directly; commercial buildings get the same with 230 V single-phase tapped off for offices and lighting. Motor control centers, pumps, compressors, conveyor drives, and HVAC chillers all expect 400 V.

European motor nameplates tell you everything needed: rated kW, 400 V (often marked “400V Δ” for delta connection), rated current, cos φ, and efficiency class (IE2/IE3/IE4). For a quick check, the rated current on the plate should match the formula within a few percent — if it does not, suspect a misread nameplate or a dual-voltage motor wired for the wrong voltage.

The 400 V kW-to-Amps Formula

Three-phase 400 V:  I = (kW × 1000) ÷ (1.732 × 400 × PF)

Worked example: a 15 kW pump motor, 400 V, cos φ 0.86: I = 15000 ÷ (1.732 × 400 × 0.86) = 15000 ÷ 595.8 = 25.2 A. Standard protection: 32 A breaker (motor-rated, type D curve) with 6 mm² copper and an overload relay set to ~26 A.

400 V Cable and Breaker Quick Reference

For copper cable in conduit at 30°C ambient (simplified, verify against IEC 60364): up to 16 A → 2.5 mm²; up to 25 A → 4 mm²; up to 32 A → 6 mm²; up to 50 A → 10 mm². Breakers for motor circuits should be type D (high inrush tolerance); for resistive/heating loads, type B or C is fine.

Worked Examples at 400 V

Example 1 — 4 kW workshop machine

A 4 kW lathe motor on 400 V three-phase, cos φ 0.82: I = 4000 ÷ (1.732 × 400 × 0.82) = 4000 ÷ 568.1 = 7.0 A. A 16 A breaker (type D for motor inrush) with 2.5 mm² copper and an overload relay set near 7.5 A is the standard workshop setup.

Example 2 — 30 kW air compressor

A 30 kW screw compressor, 400 V three-phase, cos φ 0.88: I = 30000 ÷ (1.732 × 400 × 0.88) = 30000 ÷ 609.7 = 49.2 A. Compressors run for hours, so apply the continuous factor used across IEC practice: 49.2 × 1.25 = 61.5 A → a 63 A breaker with 16 mm² copper.

Example 3 — 75 kW industrial drive

A 75 kW fan drive on 400 V three-phase, cos φ 0.9: I = 75000 ÷ (1.732 × 400 × 0.9) = 75000 ÷ 623.5 = 120.3 A. Sizing up: 120.3 × 1.25 = 150 A → a 160 A breaker with 50 mm² copper, with the drive’s own electronic overload providing motor protection.

400 V vs 415 V vs 230 V

Three voltages, three jobs. 400 V three-phase is the IEC workhorse for machinery — motors, pumps, compressors, and drives. 415 V is the legacy Commonwealth nominal for the same class of equipment; the 3.75% difference sits well inside normal supply tolerance, so one calculation method serves both. 230 V single-phase (tapped phase-to-neutral from the same 400Y/230 V service) feeds lighting, offices, and small tools. The practical rule: anything above roughly 3 kW belongs on 400 V three-phase, where the current — and therefore the cable — stays manageable. A 10 kW load draws about 17 A on 400 V three-phase but over 43 A on 230 V single-phase.

Reading a 400 V Motor Nameplate

The nameplate is the single most reliable source for your calculation inputs. A typical EU plate shows: rated power in kW, voltage (often “400V Δ” meaning delta-connected for 400 V, or “400/690V” for star-delta starting), rated current in amps, cos φ, speed in rpm, and efficiency class (IE2, IE3, or IE4). Cross-check the plate current against the formula — for example, a 15 kW, 400 V, cos φ 0.86 plate should read close to 25.2 A. If the numbers disagree by more than a few percent, the motor may be wired for the wrong voltage (star instead of delta), which is one of the most common causes of “mystery” overload trips on new installations.

Common Mistakes on 400 V Systems

Safety Notes for 400 V Industrial Work

400 V three-phase is firmly in lethal territory and demands qualified personnel, proper isolation, and lockout-tagout on every disconnect. Test for absence of voltage on all three phases — not just one — before touching conductors, because a blown fuse can leave a phase live while the equipment looks dead. Stored energy matters too: discharge DC bus capacitors in drives before working inside, and treat control circuits as live until proven otherwise. Wear arc-rated PPE when operating breakers on faulted equipment, and never bypass a safety interlock to keep production running — that shortcut is how most industrial electrical injuries happen.

Frequently Asked Questions

How many amps is 10 kW at 400 V three-phase?
About 17.0 A at PF 0.85. At PF 1 (heating loads), exactly 14.43 A.
Is 400 V the same as 415 V?
Effectively yes for calculation purposes — 415 V is the older UK/Australian nominal value, 400 V is the harmonized IEC value. Real supplies vary ±10% anyway.
What does 400Y/230 V mean?
A wye (star) service giving 400 V between phases and 230 V from any phase to neutral — one service feeding both industrial and domestic loads.
Can I run a 400 V motor on 230 V single-phase?
Only with a VFD rated for single-phase input, and the motor must be rewired from star to delta. Direct connection will not work properly.