HP to Amps at a Glance
Motor nameplates rate mechanical power in horsepower (HP), but breakers, contactors, and cables are sized in amps. One horsepower equals 746 watts of shaft power — yet the motor draws more than that from the supply, because no motor is 100% efficient and AC motors also draw reactive current. A 5 HP three-phase motor on 400 V at 0.85 power factor and 90% efficiency draws about 7.04 A full-load. The calculator above handles DC, single-phase, and three-phase motors with your actual nameplate values.
The Formulas
The 746 constant is James Watt’s definition: one horsepower is 746 watts of mechanical power at the shaft. Efficiency (eff) converts shaft power to the electrical input power the motor actually consumes, and power factor (PF) accounts for the reactive current AC motors draw on top of the useful current.
Worked Examples
Example 1 — Workshop motor: 5 HP, 400 V three-phase, PF 0.85, efficiency 0.9. I = (5 × 746) ÷ (1.732 × 400 × 0.85 × 0.9) = 3730 ÷ 530 = 7.04 A full-load current. A 16 A three-phase breaker with a 7–10 A overload relay is the standard pairing.
Example 2 — Industrial pump: 10 HP, 460 V three-phase, PF 0.88, efficiency 0.92. I = 7460 ÷ (1.732 × 460 × 0.88 × 0.92) = 7460 ÷ 645 = 11.57 A calculated. Note that the NEC Table 430.250 lists 14 A for this motor — the code table is deliberately conservative, and protection must be sized from the table value, not the calculation.
Example 3 — Single-phase compressor: 1 HP, 230 V single-phase, PF 0.8, efficiency 0.85. I = 746 ÷ (230 × 0.8 × 0.85) = 746 ÷ 156.4 = 4.77 A. NEC Table 430.248 lists 8 A for a 1 HP 230 V single-phase motor — again, size the circuit from the table.
Example 4 — DC traction motor: 2 HP, 48 V DC, efficiency 0.85. I = (2 × 746) ÷ (48 × 0.85) = 1492 ÷ 40.8 = 36.6 A. Low-voltage DC motors draw startling currents — this is why battery cables on 48 V systems are so thick.
Shaft Power vs Electrical Input
The nameplate HP is mechanical output at the shaft, not electrical input. A 5 HP motor delivers 3730 W of mechanical power, but at 90% efficiency it consumes 3730 ÷ 0.9 = 4144 W electrically — the missing 414 W becomes heat in the windings. High-efficiency (IE3/IE4) motors matter precisely because that gap costs money every hour the motor runs: at 10 hours a day, a 5-point efficiency gain on a 10 HP motor saves roughly 3.7 kWh daily.
Power factor is the second hidden tax. A motor at 0.85 PF draws about 18% more current than its real power alone requires. The extra current does no useful work but still heats cables and loads transformers — which is why kVA ratings (not kW) determine conductor sizing, and why utilities penalize large customers for low power factor.
NEC Tables vs Your Calculation
The US National Electrical Code publishes full-load current tables — 430.248 for single-phase and 430.250 for three-phase motors. These values assume worst-case efficiency and power factor, so they run higher than a calculation with good nameplate data: our 10 HP example calculates 11.57 A but the table says 14 A. For code compliance, always use the table value when sizing conductors (430.22), overload protection (430.32), and short-circuit protection (430.52). Use the calculator for understanding and estimation; use the NEC tables for the actual installation. Our breaker sizing calculator applies the NEC 430.52 motor rules directly.
Reading the Motor Nameplate
Every motor carries a nameplate, and every value on it feeds either this calculator or the protection sizing that follows. A typical plate reads something like: 3.7 kW, 400 V Δ, 7.4 A, cos φ 0.85, eff 90%, SF 1.15, S1, 1460 rpm. Here is what each field means for your calculation. kW/HP is shaft output — 3.7 kW ÷ 0.746 = 4.96 HP, the number you enter as motor power. Voltage with Δ (delta) or Y (star) tells you the winding connection at that voltage — always use the voltage matching your supply. Amps is the manufacturer’s full-load current: 7.4 A here. Check it against the calculator: 4.96 HP at 400 V, 0.85 PF, 0.9 eff gives 3700 ÷ (1.732 × 400 × 0.85 × 0.9) = 3700 ÷ 530 = 6.98 A — the small gap to the stamped 7.4 A is manufacturing margin and conservative rounding. cos φ is power factor and eff is efficiency — enter both exactly as stamped rather than guessing. SF (service factor) and duty (S1 = continuous) govern overload behavior, covered below. When a plate is missing PF or efficiency, the calculator defaults (0.85 / 0.9) are reasonable for modern TEFC motors — but stamped values always win.
Service Factor and Duty Cycle
Service factor (SF) is the motor’s built-in overload headroom. An SF of 1.15 means the motor can carry 15% beyond its rated load continuously without overheating — useful for pumps that occasionally run against higher head. Current at service-factor load is simply FLA × SF: our 7.4 A nameplate motor draws about 7.4 × 1.15 = 8.51 A at full service-factor load. Size conductors and overload relays for the load you actually expect, not just the base FLA.
Duty cycle describes the operating pattern. S1 is continuous duty — the motor reaches thermal equilibrium and stays there, which is what the FLA rating assumes. S2 is short-time duty (runs minutes, then rests), S3 is intermittent periodic duty (repeated start-run-stop cycles, like a crane hoist). Intermittent-duty motors can be smaller for the same peak load because they cool between cycles — but their protection must still handle the starting current every cycle. One code subtlety: NEC 430.32 permits overload devices sized up to 125–140% of FLA for motors with SF ≥ 1.15, recognizing that the service factor is real, usable capacity — not marketing.
Common Mistakes
- Forgetting efficiency: HP × 746 ÷ V alone understates current by 5–15%. Efficiency is not optional in the formula.
- Using HP as kW: 1 HP is 0.746 kW of mechanical power — the electrical input is higher, not lower.
- Mixing line and phase voltage: on three-phase, always use line-to-line voltage (400/415/460 V) with the √3 formula.
- Sizing wire from the calculated amps: code requires the NEC table current, which is higher. The calculated value is for understanding; the table value is for the permit.
- Ignoring starting current: full-load amps describe running current. At startup, motors draw 5–7× FLA for a few seconds — contactors and breakers must tolerate it.
Starting Current: The 6× Rule
Full-load amps describe a motor already spinning. At the instant of switch-on, the stalled rotor looks almost like a short circuit, and locked-rotor current surges to 5–7× FLA for the 2–5 seconds of run-up. Our 5 HP example at 7.04 A FLA therefore demands about 7.04 × 6 = 42.2 A at startup; the 10 HP motor at 11.57 A pulls roughly 11.57 × 6 = 69.4 A. This is normal, expected, and the reason motor circuits look “oversized” to beginners.
Three consequences follow. First, breakers must be motor-rated: a standard type-B breaker trips magnetically at 3–5× rating and will nuisance-trip on every start, while a type-D (10–20×) or motor-protection breaker rides through the surge — which is exactly what NEC 430.52’s 250% allowance is for. Second, contactors carry an AC-3 rating specifically for motor starting duty; an AC-1 (resistive) contactor of the same amp rating will weld its contacts on motor duty. Third, cables are still sized from FLA, not starting current: copper’s thermal inertia absorbs a few seconds of 6× current without damage, so the 125%-of-FLA conductor rule stands.
Large motors avoid direct-on-line starting altogether. Star-delta starters cut starting current to about one-third by starting in star (230 V per winding on a 400 V system) and switching to delta at speed; soft starters ramp voltage electronically; VFDs ramp frequency and voltage together, holding current near FLA from standstill. If your 15+ HP motor dims the lights on startup, it is asking for one of these — and for a supply authority conversation about maximum starting kVA.
When the motor is already installed, skip the arithmetic and measure: a clamp meter around one phase conductor reads true running current directly. Compare it with the nameplate FLA — a motor drawing significantly more than FLA is overloaded (check the driven load, bearings, and supply voltage balance), while one drawing far less is oversized and running at poor power factor and efficiency, wasting energy every hour. Clamp all three phases on a three-phase motor: the readings should agree within a few percent. A large imbalance points to a supply voltage problem or a developing winding fault — both worth fixing before they become a burnout. Measured current, nameplate data, and this calculator triangulate the truth.