⚡ VoltEdge

kW to Amps at 240V Calculator

Locked to 240 V — the circuit behind dryers, ovens, and central air-conditioners.

Calculator Input

LIVE  Live calculation — type and watch the result.

Dryers and ovens commonly rate 4–6 kW.
Fixed at 240 V — used for heavy US residential loads.
Use 1.0 for heating appliances, 0.9 as a default.

Conversion Result

—
Enter values to calculate

Formula Used

—

240 V Circuits at a Glance

In North American homes, 240 volts feeds the heavy hitters: electric dryers, ranges, water heaters, and central air-conditioning. These run on dedicated double-pole breakers, typically 30–50 A, because even at 240 V the currents are substantial.

At PF 1.0, 1 kW at 240 V ≈ 4.17 A. A 5 kW dryer therefore draws about 20.83 A — comfortably inside a 30 A circuit but already past what any 120 V outlet could supply. Formula: I = (kW × 1000) ÷ (240 × PF).

How 240 V Is Made: Two 120 V Legs

American homes receive split-phase service: a center-tapped transformer delivers two 120-volt legs, L1 and L2, that are 180 degrees out of phase. Each leg measures 120 V to the neutral, but across the two legs the voltages add — giving 240 V. A pure 240 V circuit connects across L1 and L2 and skips the neutral entirely, while appliances like dryers and ranges use a four-wire feed (two hots, neutral, ground) so their 120 V controls and 240 V heating elements can share one cable.

Four-wire circuits add a neutral so mixed 120/240 V appliances can run both voltages from one cable. The neutral only carries the imbalance between the two legs — if the 120 V loads on each leg are equal, the neutral current cancels toward zero. That is why a pure 240 V load, like a water heater with no 120 V controls, needs no neutral at all: the two hot legs are perfectly balanced by design. That center tap is the neutral bar you see in every residential panel.

Double-Pole Breakers

A 240 V circuit is protected by a double-pole breaker: two breaker poles joined by a single handle so both hot legs disconnect together. If one leg faults, both trip — you never want one hot leg of a 240 V circuit staying live. Modern 240 V outlets follow the NEMA 6 and 14 series: a 14-30 receptacle for dryers, a 14-50 for ranges and many EV chargers, each keyed so the wrong plug cannot fit. One rule is absolute: never cobble together two single breakers — only a factory-made double-pole unit guarantees both legs open together.

Size the wire to the breaker, not the load: 10 AWG copper for a 30 A double-pole, 8 AWG for 40 A, and 6 AWG for 50 A. Older three-wire dryer and range circuits (hot-hot-neutral, no ground) were legal in their day but are no longer installed — a new 240 V circuit always gets a separate ground.

Which Appliances Use 240 V

The dividing line is power: anything much above 2–3 kW moves to 240 V, because the current at 120 V would demand impractically thick wire and oversized breakers. A 3 kW load makes the point concrete: at 120 V it draws 25 A, but at 240 V only 12.5 A — half the current, a quarter of the resistive losses, and a much smaller breaker.

Breaker Sizing for Common 240 V Loads

For continuous loads (three hours or more), the breaker must be at least 125 percent of the load current — the 80 percent rule flipped around. Currents below assume 240 V and power factor 1.0 unless noted.

AppliancePowerCurrent125% minimumStandard double-pole
Clothes dryer5 kW20.83 A26.04 A30 A
Water heater4.5 kW18.75 A23.44 A25 A
EV charger7.2 kW30.00 A37.50 A40 A
Electric range9.6 kW40.00 A50.00 A50 A
Central AC (PF 0.85)3.5 kW17.16 A21.45 A25 A
Baseboard heater2.5 kW10.42 A13.02 A15 A

The wire must be sized to the breaker: 10 AWG copper for 30 A, 8 AWG for 40 A, 6 AWG for 50 A.

Worked Examples

Example 1 — 5 kW dryer

Current: 5,000 ÷ 240 = 20.83 A. Continuous-load minimum breaker: 20.83 × 1.25 = 26.04 A, so the next standard size is a 30 A double-pole breaker on 10 AWG copper.

Example 2 — 7.2 kW EV charger

Current: 7,200 ÷ 240 = 30 A. Minimum breaker: 30 × 1.25 = 37.5 A, so a 40 A double-pole breaker. And because charging runs for hours, the charger must be configured to draw no more than 32 A — 80 percent of the 40 A breaker.

Example 3 — 9.6 kW range

Current: 9,600 ÷ 240 = 40 A. Minimum breaker: 40 × 1.25 = 50 A, so a 50 A double-pole breaker on 6 AWG copper. Ranges cycle their elements rather than running flat-out, but they are still sized as continuous loads.

Common Mistakes

Safety Note

240 volts delivers a shock that is far more likely to be lethal than 120 V, and the fault current available at a panel is enormous. Never work inside a panel unless you are qualified, never backfeed a generator through a dryer outlet, and treat every double-pole breaker with the respect two hot legs deserve. When in doubt, an electrician’s hour costs far less than a hospital visit.

Frequently Asked Questions

1 kW at 240 V — how many amps is that?
About 4.17 amps at power factor 1.0, or roughly 4.63 A at PF 0.9.
What size breaker for a 5 kW dryer at 240 V?
5 kW draws about 20.83 A, so a 30 A double-pole breaker is the standard fit, with cable sized to match.
Is 240 V single-phase or two-phase?
It is single-phase, center-tapped: two 120 V legs 180° apart combine to 240 V across the outer conductors.
Why not run big appliances on 120 V?
A 5 kW dryer would need over 41 A at 120 V — thicker wire, bigger breakers, more heat. 240 V halves the current and the losses.
Can I run a 240 V dryer on a 30 A breaker wired with 12 AWG?
No. A 30 A breaker requires 10 AWG copper minimum — 12 AWG is only rated for 20 A, and the breaker would let the wire overheat.
Why does my 30 A EV charger need a 40 A breaker?
EV charging runs for hours, making it a continuous load. Code requires the breaker to be at least 125 percent of the continuous current: 30 × 1.25 = 37.5 A, so 40 A is the next standard size.