kVA to Amps at a Glance
Generators, transformers, and UPS units are rated in kVA (apparent power), but breakers and cables care about amps. This conversion bridges the two. A 10 kVA generator on 400 V three-phase delivers about 14.4 A per phase — that is the number your distribution board must handle.
The Formulas
Worked example: a 45 kVA generator, 415 V three-phase: I = 45000 ÷ (1.732 × 415) = 62.6 A per phase.
kVA vs kW — Why Generators Use kVA
kVA measures apparent power (everything the generator must supply, including reactive current); kW measures only the useful real power. The ratio between them is the power factor. A generator rated 100 kVA at 0.8 PF delivers 80 kW of real power — but its windings and breakers must handle the full 100 kVA worth of current. Always size conductors from kVA, not kW.