Kilowatts to Amp Hours Calculator

Turn a power rating into battery capacity — see how many amp-hours a kilowatt load consumes over a given run time.

Calculator Input

LIVE  Live calculation — type and watch the result.

The load you want to run — e.g. a 5 kW inverter load.
Your bank voltage: 12, 24 or 48 V are the usual setups.
How long the load must run between charges.

Amp-Hours Required

—
Enter values to calculate

Formula Used

—

What an Amp-Hour Really Means

An amp-hour is a unit of electric charge, and the definition is pleasantly literal: one amp-hour is one amp flowing for one hour. It is equally correct to say that a 100 Ah battery can deliver 5 amps for 20 hours or 20 amps for 5 hours — charge is charge, and the product of current and time is what counts.

Think of it as the size of the fuel tank, measured in electrons rather than litres. A battery’s amp-hour rating tells you how much charge it can hand over before it is empty — but, and this is the part that trips people up, it says nothing about energy until you pair it with a voltage. Two batteries can both be rated 100 Ah and store very different amounts of energy, which is why the next section exists.

How the Amp-Hours Calculation Works

1

Enter the load in kilowatts

The total power your equipment draws while running.

2

Enter the battery voltage

The nominal voltage of your battery bank.

3

Enter the run time

How many hours the load must be supported.

4

Read the amp-hours

The calculator also shows the total watt-hours alongside.

Amp-Hours vs Watt-Hours

Watt-hours measure energy; amp-hours measure charge at a particular voltage. The bridge between them is a single multiplication:

Energy stored: Wh = Ah × V

A 100 Ah battery at 12 V stores 100 × 12 = 1,200 Wh, while a 100 Ah battery at 48 V stores 100 × 48 = 4,800 Wh — four times the energy for the same amp-hour rating. Comparing battery banks by amp-hours alone is meaningless unless the voltages match: always convert to watt-hours when the systems differ.

100 Ah bank voltageEnergy stored
12 V1,200 Wh
24 V2,400 Wh
48 V4,800 Wh

Going the other direction is just as common. A solar array quoted in watts feeding a battery bank quoted in amp-hours needs the same conversion — divide the daily watt-hour harvest by the bank voltage to find the amp-hours the bank must accept.

Amp-Hours Formulas

kW to amp-hours: Ah = (kW × 1000 × hours) ÷ V

Convert to watts, multiply by the hours to get watt-hours, then divide by the bank voltage.

Watt-hours (intermediate step): Wh = kW × 1000 × hours

Energy first, capacity second — watt-hours is the energy the bank must store.

Reverse (amp-hours → kW): kW = (Ah × V) ÷ (1000 × hours)

Going backwards: multiply amp-hours by voltage to get watt-hours, then divide by hours and 1000.

Runtime: How Long Will the Battery Last?

Runtime is the reverse of the capacity calculation: divide the amp-hours by the load current.

Battery runtime: hours = Ah ÷ load amps

For a 100 Ah, 12 V battery:

LoadDraw at 12 VTheoretical runtimeUsable (50% DoD lead-acid)
1 A12 W100 h50 h
2 A24 W50 h25 h
5 A60 W20 h10 h
10 A120 W10 h5 h
20 A240 W5 h2.5 h

These are theoretical figures. Real runtime is shorter: lead-acid batteries should not be discharged past about half their capacity, heavy discharge rates eat into usable capacity (see below), and an inverter feeding AC loads wastes another 10 to 15 percent.

The Peukert Effect, Briefly

Lead-acid chemistry delivers less total capacity the harder you pull. A 100 Ah rating is usually measured over a slow 20-hour discharge; draw 20 amps from the same battery and you may only recover 70 to 80 amp-hours before the voltage collapses. Lithium chemistries barely suffer from this, which is one reason they have taken over off-grid work despite the higher price.

Sizing Batteries with Amp-Hours

Off-grid cabins, RVs, boats, and backup systems all start from this one number: how many amp-hours the load needs over the autonomy period. A 5 kW load on a 24 V bank for 5 hours needs (5 × 1000 × 5) ÷ 24 = 1041.67 Ah — that is the raw figure before adding any safety margin.

Real banks get sized above the raw number: lead-acid should not be discharged past ~50%, and lithium banks want a 10–20% headroom for aging and cold weather. Solar designers then work backwards from the watt-hours figure to size the panel array that must refill the bank each day.

Solar and Off-Grid Sizing Example

Start from energy, not amp-hours. Suppose a cabin consumes 1.5 kWh per day and needs two days of autonomy: that is 3,000 Wh of usable energy. A lead-acid bank should only be discharged to about half, so the bank must store 3,000 ÷ 0.50 = 6,000 Wh. At a 48 V bank voltage, that is 6,000 ÷ 48 = 125 Ah. With lithium, where 80 percent discharge is routine, the same need calls for 3,000 ÷ 0.80 = 3,750 Wh, or 3,750 ÷ 48 ≈ 78 Ah — typically rounded up to an 80 Ah bank. The solar designer then checks that the panel array can replace 1.5 kWh on an average day.

Worked Examples

Example 1 — accounting for inverter losses

A 1 kW AC load must run for 4 hours from a 12 V bank through a 90-percent-efficient inverter. The raw figure is (1 × 1000 × 4) ÷ 12 = 333.33 Ah. The inverter wastes a tenth, so divide by its efficiency: 333.33 ÷ 0.90 = 370.37 Ah — the theoretical minimum the bank must hold.

Example 2 — moving to a higher bank voltage

A 2.5 kW pump running 3 hours a day on a 48 V bank needs (2.5 × 1000 × 3) ÷ 48 = 156.25 Ah per day. The same energy at 12 V would demand over 600 Ah, which is why larger systems standardize on 48 V: currents stay manageable and cables stay thin.

Example 3 — runtime from a known bank

A 200 Ah battery feeding a steady 25 A load lasts 200 ÷ 25 = 8 hours in theory. On lead-acid, respecting the 50 percent discharge rule, plan on 4 usable hours.

Common Mistakes

Safety Note

Batteries store serious energy and deserve respect: fuse the positive cable close to the battery, ventilate lead-acid banks because charging releases hydrogen, and keep metal tools away from terminals. A shorted battery can weld a wrench in a fraction of a second.

Frequently Asked Questions

How do you convert kW to amp-hours?
Multiply kW by 1000 and by the hours, then divide by the battery voltage: Ah = (kW × 1000 × h) ÷ V.
What is the difference between Ah and Wh?
Watt-hours measure energy; amp-hours measure charge at a specific voltage. Multiply Ah by the voltage to get Wh — Wh is what you pay for on a bill.
How many amp-hours is 1 kW for 1 hour?
On a 12 V bank: 83.33 Ah. On 24 V: 41.67 Ah. On 48 V: 20.83 Ah — higher bank voltage means fewer amp-hours for the same energy.
Do I need to add a safety margin?
Yes. Add 20–50% depending on battery chemistry and how deep you are willing to discharge. This calculator gives the theoretical minimum.
Does inverter efficiency change the result?
It does in real systems. A 90%-efficient inverter draws about 11% more from the batteries than the AC load rating suggests — divide your result by the inverter efficiency.
Can I connect batteries in series to get more amp-hours?
No. Series connections add voltage while amp-hours stay the same; parallel connections add amp-hours while voltage stays the same. Two 100 Ah 12 V batteries in series give 100 Ah at 24 V; in parallel they give 200 Ah at 12 V.
Is it safe to discharge a lead-acid battery to zero?
It works once or twice, then the battery is ruined. Keep regular discharges above 50 percent — below that, sulfation permanently eats capacity.