What an Amp-Hour Really Means
An amp-hour is a unit of electric charge, and the definition is pleasantly literal: one amp-hour is one amp flowing for one hour. It is equally correct to say that a 100 Ah battery can deliver 5 amps for 20 hours or 20 amps for 5 hours — charge is charge, and the product of current and time is what counts.
Think of it as the size of the fuel tank, measured in electrons rather than litres. A battery’s amp-hour rating tells you how much charge it can hand over before it is empty — but, and this is the part that trips people up, it says nothing about energy until you pair it with a voltage. Two batteries can both be rated 100 Ah and store very different amounts of energy, which is why the next section exists.
How the Amp-Hours Calculation Works
Enter the load in kilowatts
The total power your equipment draws while running.
Enter the battery voltage
The nominal voltage of your battery bank.
Enter the run time
How many hours the load must be supported.
Read the amp-hours
The calculator also shows the total watt-hours alongside.
Amp-Hours vs Watt-Hours
Watt-hours measure energy; amp-hours measure charge at a particular voltage. The bridge between them is a single multiplication:
A 100 Ah battery at 12 V stores 100 × 12 = 1,200 Wh, while a 100 Ah battery at 48 V stores 100 × 48 = 4,800 Wh — four times the energy for the same amp-hour rating. Comparing battery banks by amp-hours alone is meaningless unless the voltages match: always convert to watt-hours when the systems differ.
| 100 Ah bank voltage | Energy stored |
|---|---|
| 12 V | 1,200 Wh |
| 24 V | 2,400 Wh |
| 48 V | 4,800 Wh |
Going the other direction is just as common. A solar array quoted in watts feeding a battery bank quoted in amp-hours needs the same conversion — divide the daily watt-hour harvest by the bank voltage to find the amp-hours the bank must accept.
Amp-Hours Formulas
Convert to watts, multiply by the hours to get watt-hours, then divide by the bank voltage.
Energy first, capacity second — watt-hours is the energy the bank must store.
Going backwards: multiply amp-hours by voltage to get watt-hours, then divide by hours and 1000.
Runtime: How Long Will the Battery Last?
Runtime is the reverse of the capacity calculation: divide the amp-hours by the load current.
For a 100 Ah, 12 V battery:
| Load | Draw at 12 V | Theoretical runtime | Usable (50% DoD lead-acid) |
|---|---|---|---|
| 1 A | 12 W | 100 h | 50 h |
| 2 A | 24 W | 50 h | 25 h |
| 5 A | 60 W | 20 h | 10 h |
| 10 A | 120 W | 10 h | 5 h |
| 20 A | 240 W | 5 h | 2.5 h |
These are theoretical figures. Real runtime is shorter: lead-acid batteries should not be discharged past about half their capacity, heavy discharge rates eat into usable capacity (see below), and an inverter feeding AC loads wastes another 10 to 15 percent.
The Peukert Effect, Briefly
Lead-acid chemistry delivers less total capacity the harder you pull. A 100 Ah rating is usually measured over a slow 20-hour discharge; draw 20 amps from the same battery and you may only recover 70 to 80 amp-hours before the voltage collapses. Lithium chemistries barely suffer from this, which is one reason they have taken over off-grid work despite the higher price.
Sizing Batteries with Amp-Hours
Off-grid cabins, RVs, boats, and backup systems all start from this one number: how many amp-hours the load needs over the autonomy period. A 5 kW load on a 24 V bank for 5 hours needs (5 × 1000 × 5) ÷ 24 = 1041.67 Ah — that is the raw figure before adding any safety margin.
Real banks get sized above the raw number: lead-acid should not be discharged past ~50%, and lithium banks want a 10–20% headroom for aging and cold weather. Solar designers then work backwards from the watt-hours figure to size the panel array that must refill the bank each day.
Solar and Off-Grid Sizing Example
Start from energy, not amp-hours. Suppose a cabin consumes 1.5 kWh per day and needs two days of autonomy: that is 3,000 Wh of usable energy. A lead-acid bank should only be discharged to about half, so the bank must store 3,000 ÷ 0.50 = 6,000 Wh. At a 48 V bank voltage, that is 6,000 ÷ 48 = 125 Ah. With lithium, where 80 percent discharge is routine, the same need calls for 3,000 ÷ 0.80 = 3,750 Wh, or 3,750 ÷ 48 ≈ 78 Ah — typically rounded up to an 80 Ah bank. The solar designer then checks that the panel array can replace 1.5 kWh on an average day.
Worked Examples
Example 1 — accounting for inverter losses
A 1 kW AC load must run for 4 hours from a 12 V bank through a 90-percent-efficient inverter. The raw figure is (1 × 1000 × 4) ÷ 12 = 333.33 Ah. The inverter wastes a tenth, so divide by its efficiency: 333.33 ÷ 0.90 = 370.37 Ah — the theoretical minimum the bank must hold.
Example 2 — moving to a higher bank voltage
A 2.5 kW pump running 3 hours a day on a 48 V bank needs (2.5 × 1000 × 3) ÷ 48 = 156.25 Ah per day. The same energy at 12 V would demand over 600 Ah, which is why larger systems standardize on 48 V: currents stay manageable and cables stay thin.
Example 3 — runtime from a known bank
A 200 Ah battery feeding a steady 25 A load lasts 200 ÷ 25 = 8 hours in theory. On lead-acid, respecting the 50 percent discharge rule, plan on 4 usable hours.
Common Mistakes
- Comparing amp-hours across different voltages — 100 Ah at 48 V holds four times the energy of 100 Ah at 12 V.
- Forgetting depth of discharge: a lead-acid bank delivers roughly half its printed rating in practice.
- Ignoring inverter losses of 10 to 15 percent whenever the load is AC rather than DC.
- Assuming the printed Ah is available at any discharge rate — lead-acid capacity shrinks under heavy loads (the Peukert effect above).
- Wiring batteries in series and expecting the amp-hours to add — series strings add voltage; only parallel strings add amp-hours.
Safety Note
Batteries store serious energy and deserve respect: fuse the positive cable close to the battery, ventilate lead-acid banks because charging releases hydrogen, and keep metal tools away from terminals. A shorted battery can weld a wrench in a fraction of a second.