120 V Circuits at a Glance
120 volts is the everyday outlet voltage across the United States and Canada, feeding lighting, small appliances, electronics, and portable heaters. Because the voltage is relatively low, currents run high — that is why 15 A and 20 A breakers are the norm on these branch circuits.
At PF 1.0, 1 kW at 120 V = 8.33 A. So a 1.5 kW heater draws 12.5 A, which already eats most of a 15 A circuit — one more appliance on the same breaker and it trips. Formula: I = (kW × 1000) ÷ (120 × PF).
Standard 15 A and 20 A Branch Circuits
American homes are wired with two workhorse circuits. The 15-amp circuit feeds general-purpose receptacles and lighting — bedrooms, living rooms, hallways. The 20-amp circuit appears where heavier loads live: kitchen countertops, bathrooms, garages, and laundry areas, where electrical code requires it. A 15 A circuit carries at most 1,800 W (15 × 120), and a 20 A circuit 2,400 W — but, as the next section explains, you should not plan to use all of it.
The 20 A circuit is required by code in several places: kitchen countertop receptacles, bathroom outlets, garage receptacles, and the laundry area each get dedicated 20 A runs. Dedicated means exactly that — one appliance circuit, not shared with the hallway lights. Bedrooms and living rooms, with their lighter loads, stay on 15 A circuits, which keeps the wiring costs down where the heavy current is never needed.
The 80% Continuous-Load Rule
Electrical code treats any load running three hours or more as continuous, and continuous loads may only use 80 percent of a circuit’s rating. Heat builds up over time, and the margin keeps breakers from tripping on a long winter evening.
- 15 A circuit: 15 × 0.80 = 12 A, or 1,440 W continuous.
- 20 A circuit: 20 × 0.80 = 16 A, or 1,920 W continuous.
This is why a 1,500 W space heater (12.5 A) should not live on a 15 A bedroom circuit: it fits the breaker’s absolute rating but breaks the 1,440 W continuous limit. Give it a 20 A circuit instead.
NEMA 5-15 Outlets
The familiar American wall outlet is the NEMA 5-15: two flat slots plus a round ground hole, rated 15 amps at 125 volts. The neutral slot is slightly wider than the hot one — that polarization is a safety feature, not a manufacturing quirk. Its big sibling, the NEMA 5-20, has a T-shaped neutral slot to accept 20-amp plugs. Ground-fault (GFCI) protection is required on these outlets in kitchens, bathrooms, garages, basements, and outdoors, while arc-fault (AFCI) protection covers most living spaces. Tamper-resistant shutters are standard on new receptacles — a small spring-loaded detail that keeps curious fingers out.
Wire Gauge Guidance
Breaker and wire are a matched pair: the wire must safely carry anything the breaker will allow. For copper conductors, the standard pairings are:
| Circuit | Copper wire |
|---|---|
| 15 A | 14 AWG |
| 20 A | 12 AWG |
| 30 A | 10 AWG |
Never put a 20 A breaker on 14 AWG wire — the breaker would allow more current than the wire can safely carry. On long runs (over roughly 100 feet), electricians upsize the wire to keep voltage drop under about 3 percent, because an appliance at the far end of a long thin cable effectively sees less than 120 V.
Amps for Common Appliances at 120 V
Computed with I = watts ÷ 120 (resistive loads, power factor 1.0):
| Appliance | Typical watts | Amps at 120 V |
|---|---|---|
| Phone charger | 15 W | 0.12 A |
| Laptop charger | 90 W | 0.75 A |
| LED TV | 100 W | 0.83 A |
| Microwave | 1,000 W | 8.33 A (9.26 at PF 0.9) |
| Coffee maker | 1,200 W | 10.00 A |
| Toaster | 1,400 W | 11.67 A |
| Space heater | 1,500 W | 12.50 A |
| Hair dryer | 1,875 W | 15.62 A |
Motors and electronics with switching supplies draw slightly more than the simple division suggests — the microwave row shows the difference a 0.9 power factor makes.
Worked Examples
Example 1 — bedroom heater on a 15 A circuit
A 1,500 W space heater (12.5 A) plus a 100 W TV (0.83 A) and a 60 W lamp (0.50 A) total 13.83 A — under the 15 A breaker rating. But a heater running all evening is a continuous load, and 13.83 A exceeds the 12 A continuous limit. The circuit is overloaded on paper: the heater belongs on its own 20 A circuit.
Example 2 — kitchen showdown on a 20 A circuit
A 1,000 W microwave (8.33 A) and a 1,400 W toaster (11.67 A) started together draw exactly 20 A. The breaker will trip — and even if it held, the combination exceeds the 16 A continuous ceiling. Run them one at a time, or better, give the microwave its own dedicated circuit.
Common Mistakes
- Chaining power strips behind a space heater or hair dryer — the strip’s thin cord becomes the weakest link and the first thing to melt.
- Treating a 20 A breaker as permission for 20 A of continuous load — the real ceiling is 16 A.
- Swapping a tripping breaker for a bigger one without checking the wire gauge — a 20 A breaker on 14 AWG wire is a fire setup.
- Assuming every kitchen outlet is its own circuit — countertop outlets often share one 20 A run, and two heat-producing appliances on it will trip the breaker.
- Using lightweight extension cords as permanent wiring for heaters and air conditioners.
Safety Note
120 volts is low enough to feel familiar and high enough to kill. Switch the breaker off and test before touching anything, keep water away from outlets and cords, and call an electrician for anything inside the panel. If a breaker trips repeatedly, it is doing its job — find the overload instead of defeating the protection.