kW to Amps at 208V Calculator

Locked to 208 V — the US commercial three-phase standard (208Y/120 V).

Calculator Input

LIVE  Live calculation — type and watch the result.

Rooftop HVAC units and commercial motors are the typical 208 V loads.
Fixed at 208 V line-to-line, the common US commercial supply.
Motors typically run 0.75–0.9. Use the nameplate value when available.

Conversion Result

—
Enter values to calculate

Formula Used

—

208 V Three-Phase at a Glance

208 volts three-phase is the workhorse of American commercial buildings. It comes from a 208Y/120 V wye service: 208 V between any two phases for heavy equipment, and 120 V from any phase to neutral for lighting and receptacles. If you manage a restaurant, office, or retail space in the US, most of your big loads run on 208 V three-phase.

At PF 0.85, 1 kW at 208 V three-phase ≈ 3.27 A. A 15 kW rooftop HVAC unit pulls roughly 49 A, which is why commercial panels feed these units with dedicated 60 A breakers. Formula: I = (kW × 1000) ÷ (1.732 × 208 × PF).

Where 208 V Three-Phase Is Used

The 208Y/120 V system dominates US commercial construction because it delivers two voltages from one service. The 120 V leg powers lighting, computers, and general receptacles, while the 208 V three-phase side runs rooftop air-conditioners, commercial kitchen equipment, elevators, and motors up to about 25 hp. Warehouses, shopping centers, schools, and hospitals across North America are wired this way.

One quirk of 208 V: it is derived from a 120 V wye, so the phase-to-phase voltage is 120 × √3 = 207.8 V (rounded to 208). Equipment nameplated “208-230 V” is designed to tolerate this range, which is why you will see dual-rated motors and HVAC units. When calculating, always use 208 V (not 230 V) for the most conservative — and code-compliant — current value.

The 208 V kW-to-Amps Formula

Three-phase power is √3 × line voltage × line current × power factor. Rearranged for current:

Three-phase 208 V:  I = (kW × 1000) ÷ (1.732 × 208 × PF)

Worked example: a 12 kW commercial oven on 208 V three-phase, PF 0.9: I = 12000 ÷ (1.732 × 208 × 0.9) = 12000 ÷ 324.2 = 37.0 A. Per NEC 210.19, continuous loads need 125% sizing: 37 × 1.25 = 46.3 A → a 50 A breaker with 6 AWG copper.

208 V vs 240 V vs 480 V

US facilities often have a choice of services. At the same kilowatts, 480 V draws less than half the current of 208 V, which means smaller wire and breakers — the reason large industrials prefer 480 V. But 208 V equipment is cheaper and more widely stocked for light commercial use. Rule of thumb: under ~50 kW total load, 208 V is usually the economical choice; above that, get a 480 V service quoted.

Worked Examples at 208 V

Example 1 — 5 kW commercial lighting panel

A small office lighting panel draws 5 kW on 208 V three-phase at PF 0.9 (typical for LED drivers with correction). I = 5000 ÷ (1.732 × 208 × 0.9) = 5000 ÷ 324.2 = 15.4 A. Lighting runs for hours, so it counts as a continuous load: 15.4 × 1.25 = 19.3 A → a 20 A breaker with 12 AWG copper.

Example 2 — 20 kW rooftop HVAC unit

A rooftop air-conditioner nameplated 20 kW, 208 V three-phase, PF 0.87: I = 20000 ÷ (1.732 × 208 × 0.87) = 20000 ÷ 313.4 = 63.8 A. HVAC compressors cycle but the feeder is sized for continuous duty: 63.8 × 1.25 = 79.8 A → an 80 A breaker with 4 AWG copper.

Example 3 — 50 kW commercial kitchen

A restaurant kitchen with electric ovens and fryers totaling 50 kW on 208 V three-phase, PF 0.85: I = 50000 ÷ (1.732 × 208 × 0.85) = 50000 ÷ 306.2 = 163.3 A. With the 125% continuous factor: 163.3 × 1.25 = 204 A → a 225 A breaker feeding a sub-panel.

Wire and Breaker Sizing for 208 V

On 208 V commercial feeders, breaker and conductor are sized together under the NEC. The breaker protects the wire, so the wire’s ampacity must meet or exceed the breaker rating. Standard copper pairings (75°C column, verify against the current NEC):

BreakerCopper wireTypical 208 V load
20 A12 AWGLighting panels, small receptacle circuits
30 A10 AWGSmall water heaters, 5 kW equipment
60 A6 AWG15 kW HVAC units
80 A4 AWG20 kW rooftop units
100 A3 AWG25 kW commercial ovens
150 A1/0 AWG40 kW kitchen feeders

Remember the two-step workflow: first compute the load current with the three-phase formula, then multiply by 1.25 for continuous loads before selecting the next standard breaker size up. On long conduit runs through hot ceiling spaces, apply ambient-temperature and conduit-fill derating from NEC 310 — a wire that is fine at 30°C may need upsizing at 45°C.

Common Mistakes on 208 V Systems

Safety Notes for 208 V Commercial Work

208 V three-phase demands the same respect as any commercial service. Only qualified persons should open panels or land conductors — arc-flash energy at 208 V is lower than at 480 V but still capable of serious burns. Verify absence of voltage with a rated tester on every phase before touching conductors, follow lockout-tagout on disconnects feeding rooftop units, and never defeat an interlock to “just check something quickly.” If a breaker feeding 208 V equipment trips repeatedly, the protection is doing its job: find the overload, the failing motor, or the loose connection instead of upsizing the breaker.

Frequently Asked Questions

How many amps is 10 kW at 208 V three-phase?
About 32.7 A at PF 0.85, or 30.9 A at PF 0.9. Always use the equipment’s actual power factor from its nameplate.
Is 208 V single-phase or three-phase?
Both exist. 208 V three-phase is the commercial standard; 208 V single-phase (two legs of the wye) feeds smaller commercial loads like water heaters.
Can 230 V equipment run on 208 V?
Usually yes if nameplated “208-230 V”. Pure 230 V equipment may run hot or underperform — check the nameplate rating first.
What wire size for 30 A at 208 V?
10 AWG copper (rated 30 A at 60°C) for non-continuous loads; 8 AWG if the load runs 3+ hours continuously per NEC derating.