⚡ VoltEdge

Voltage Drop Calculator

Check wire size and run length against NEC limits.

Calculator Input

LIVE  Live calculation — type and watch the result.

Full-load current of the circuit.
Distance from source to load, one way — the calculator doubles it.
Nominal voltage at the source: 120, 230, 400, etc.
Copper resistance per NEC Chapter 9, Table 8 (ohms per 1000 ft).

Voltage Drop

—
Enter values to calculate

Assessment

—

Voltage Drop at a Glance

Every wire has resistance, and current flowing through resistance causes voltage to be lost along the run — this is voltage drop. The fix is simple to state: use thicker wire or a shorter run. The NEC recommends keeping drop under 3% for branch circuits and under 5% total (feeder + branch combined). A 20 A load on 100 ft of 12 AWG copper at 120 V loses 7.72 V — that is 6.43%, well over the limit.

Voltage drop matters because undervoltage makes motors run hot, lights dim, and electronics misbehave — while the lost energy heats the wire itself. Long runs to outbuildings, garden lighting, well pumps, and solar arrays are the classic trouble spots. The calculator above uses NEC Chapter 9 Table 8 copper resistances for DC, single-phase, and three-phase circuits; the guide below explains the formulas, shows verified worked examples, and covers how to fix excessive drop.

The Formulas

DC and single-phase (2-wire):  Vd = 2 × I × R × L ÷ 1000
Three-phase:  Vd = √3 × I × R × L ÷ 1000
Percentage drop:  %Vd = Vd ÷ V × 100

I is current in amps, R is the conductor resistance in ohms per 1000 ft (from the wire size table), L is the one-way length in feet, and V is the supply voltage. The factor of 2 on DC and single-phase accounts for the round trip — current travels out on one conductor and back on the other, so the total wire in the circuit is twice the one-way distance. On three-phase the √3 factor replaces it. Resistance values come from NEC Chapter 9, Table 8 for uncoated copper at 75°C: 14 AWG is 3.07 Ω/kft, 12 AWG is 1.93, 10 AWG is 1.21, 8 AWG is 0.764, 6 AWG is 0.491, 4 AWG is 0.308, 2 AWG is 0.194, and 4/0 AWG is 0.0608.

Worked Examples

Example 1 — Long 120 V run (single-phase): 20 A load, 100 ft one-way, 12 AWG (R = 1.93). Vd = 2 × 20 × 1.93 × 100 ÷ 1000 = 7.72 V. %Vd = 7.72 ÷ 120 × 100 = 6.43% — fails both the 3% and 5% guidance. Upsize to 8 AWG: Vd = 2 × 20 × 0.764 × 100 ÷ 1000 = 3.06 V = 2.55% — passes.

Example 2 — Same run at 240 V: 7.72 V ÷ 240 × 100 = 3.22% — marginal: over the 3% branch guidance but inside the 5% combined limit. This shows why higher voltage is so effective against drop — the volts lost are identical, but they are a smaller fraction of a larger supply.

Example 3 — Lighting circuit: 15 A, 50 ft one-way, 14 AWG (R = 3.07) at 120 V. Vd = 2 × 15 × 3.07 × 50 ÷ 1000 = 4.61 V = 3.84% — over 3%. One size up (12 AWG) gives 2.90 V = 2.41%.

Example 4 — Three-phase feeder: 30 A, 200 ft one-way, 10 AWG (R = 1.21) at 480 V. Vd = 1.732 × 30 × 1.21 × 200 ÷ 1000 = 12.57 V = 2.62% — within the 3% guidance, acceptable.

Example 5 — Low-voltage DC (the danger zone): 10 A, 25 ft one-way, 12 AWG at 24 V. Vd = 2 × 10 × 1.93 × 25 ÷ 1000 = 0.97 V = 4.02%. Less than one volt lost — yet over 4% of a 24 V supply. Low-voltage DC systems need dramatically thicker wire than the amps alone suggest.

Copper Resistance Reference (NEC Chapter 9, Table 8)

The calculator uses these DC resistance values for uncoated copper at 75°C, in ohms per 1000 feet. Resistance — and therefore voltage drop — falls by roughly half every 3 AWG sizes:

Wire SizeΩ per 1000 ftWire SizeΩ per 1000 ft
14 AWG3.071 AWG0.154
12 AWG1.931/0 AWG0.122
10 AWG1.212/0 AWG0.0967
8 AWG0.7643/0 AWG0.0766
6 AWG0.4914/0 AWG0.0608
4 AWG0.308
3 AWG0.245
2 AWG0.194

Voltage Drop in Solar and Low-Voltage Systems

Low-voltage DC is where voltage drop bites hardest, because every lost volt is a large percentage of a small supply. A 3% budget on a 12 V system is just 0.36 V — a 10 A load over 20 ft of 12 AWG already loses 0.77 V (6.4%). Solar installers handle this three ways: keep battery-to-inverter cables as short as physically possible, oversize them well beyond what ampacity requires (2/0 or 4/0 AWG is normal for 3 kW+ inverters on 48 V), and prefer 48 V battery banks over 12 V for anything above a few hundred watts — quadrupling the voltage quarters the percentage drop for the same power. If your charge controller reports low battery voltage while the batteries themselves measure fine, unwanted drop in the cabling is the first suspect.

The NEC 3% / 5% Guidance Explained

NEC 210.19 and 215.2 recommend — not mandate — that branch-circuit voltage drop stay under 3% and that feeder plus branch combined stay under 5%, for “reasonable efficiency of operation.” It is guidance rather than a hard rule, but inspectors, engineers, and equipment warranties all treat it as the standard. Sensitive electronic loads and motors deserve the stricter end: a motor starting at 90% voltage draws higher current and runs hotter, shortening its life. When in doubt, design to 3% on the branch and keep the total under 5%.

What Affects Voltage Drop

How to Fix Excessive Drop

1) Upsize the wire — the standard fix. Going from 12 AWG to 10 AWG cuts drop by 37%. 2) Shorten the run — relocate the panel or subpanel closer to the load. 3) Raise the voltage — a 240 V circuit has one-quarter the percentage drop of a 120 V circuit carrying the same power (half the current, twice the supply voltage). 4) Split the load — two circuits at half current each have half the drop per circuit. Always re-check with the wire size calculator that ampacity still works after any change.

Common Mistakes

Keep Calculating

Voltage drop and ampacity are the two halves of wire selection: check current capacity with the wire size calculator, protect the circuit with the breaker sizing calculator, find load current from power with the kW to amps calculator, and read motor nameplates on the motor current page.

Frequently Asked Questions

What is an acceptable voltage drop?
The NEC recommends max 3% on branch circuits and 5% total (feeder + branch). Under 3% is ideal; 3–5% is acceptable for the combined run; over 5% should be corrected.
How do I calculate voltage drop manually?
Single-phase: Vd = 2 × amps × resistance × one-way feet ÷ 1000, using the Ω/kft value for your wire size. Then divide by supply voltage × 100 for the percentage.
Does voltage drop matter for short runs?
Rarely — under about 30 ft at 120/230 V with correctly sized wire, drop is usually under 1%. It becomes critical on long runs and all low-voltage DC.
What wire size for 100 ft at 20 amps?
For ampacity, 12 AWG copper suffices — but at 120 V the drop is 6.43%, so use 8 AWG (2.55%) to satisfy voltage drop. At 240 V, 10 AWG gives 2.03%.
Is voltage drop worse on 120 V or 240 V?
The volts lost are identical for the same current and wire, but 120 V suffers twice the percentage drop — and for the same power, 120 V carries twice the current, making it roughly 4× worse in practice.
Can voltage drop damage equipment?
Yes — motors draw more current at low voltage and overheat, compressors may fail to start, and electronics can reset or malfunction. Chronic undervoltage shortens equipment life.
Do I use one-way or round-trip distance?
One-way. The formula’s ×2 (or √3 for three-phase) already accounts for the return path.
Does aluminum wire change the calculation?
Yes — aluminum has higher resistance per AWG (e.g., 12 AWG aluminum is 3.18 Ω/kft vs 1.93 for copper). Use the aluminum column of NEC Table 8 or simply upsize.