Watts to Amps at a Glance
To convert watts to amps, divide watts by volts. On AC circuits you also divide by the power factor, and on three-phase circuits you divide by an extra 1.732 (√3). That is the entire conversion in one sentence: amps = watts ÷ volts, adjusted for circuit type. A 1500 W heater on 230 V single-phase draws 1500 ÷ 230 = 6.52 A.
This is the reverse of the amps-to-watts conversion and one of the most-used calculations in electrical work. Appliance ratings are printed in watts, but breakers, wires, and fuses are rated in amps — so every time you ask “can I plug this into that circuit,” you are doing a watts-to-amps conversion. The calculator above handles DC, single-phase, and three-phase automatically; the article below explains the formulas, shows worked examples, and covers the mistakes that trip people up.
The Three Formulas
Here P is power in watts, V is voltage in volts, and PF is power factor (1 for DC and resistive loads like heaters and incandescent bulbs, typically 0.8–0.95 for motors). Power factor only applies to AC: it accounts for the reactive current that motors and transformers draw on top of the useful current. Use PF = 1 whenever you are unsure and the load is resistive — the answer will be exact. For motors, check the nameplate for “cos φ” or use 0.85 as a reasonable estimate.
Worked Examples
Example 1 — Workshop heater (single-phase): a 1500 W heater on 230 V, PF 1. I = 1500 ÷ (230 × 1) = 1500 ÷ 230 = 6.52 A. A standard 10 A or 13 A socket handles this comfortably.
Example 2 — Industrial motor (three-phase): a 2.2 kW (2200 W) motor on 400 V three-phase, PF 0.83. I = 2200 ÷ (1.732 × 400 × 0.83) = 2200 ÷ 575.0 = 3.83 A full-load current. Size the overload relay at 105–115% of this value and the breaker per your local motor rules.
Example 3 — Off-grid DC (solar battery system): a 600 W inverter load on a 48 V battery bank. I = 600 ÷ 48 = 12.5 A from the batteries. This is why low-voltage DC wiring needs surprisingly thick cable — the same 600 W at 230 V AC would be only 2.6 A.
Example 4 — Household bulb: a 100 W bulb on 120 V. I = 100 ÷ 120 = 0.83 A. Fifteen such bulbs on one circuit draw 12.5 A — already close to a 15 A breaker’s limit.
Quick Reference: Common Wattages to Amps
For fast lookups, here are everyday wattages converted at common voltages — single-phase at PF 1, and three-phase at 400 V, PF 0.85:
| Watts | 120 V | 230 V | 400 V 3-phase |
|---|---|---|---|
| 60 W | 0.50 A | 0.26 A | 0.10 A |
| 100 W | 0.83 A | 0.43 A | 0.17 A |
| 500 W | 4.17 A | 2.17 A | 0.85 A |
| 1000 W | 8.33 A | 4.35 A | 1.70 A |
| 1500 W | 12.50 A | 6.52 A | 2.55 A |
| 2000 W | 16.67 A | 8.70 A | 3.40 A |
| 3000 W | 25.00 A | 13.04 A | 5.09 A |
DC Systems: Why the Amps Get Big Fast
The same watts produce wildly different amps depending on voltage, and nowhere is this more dramatic than in low-voltage DC. Because I = P ÷ V, halving the voltage doubles the current for the same power:
| 1000 W load | Current | Typical wire needed |
|---|---|---|
| 12 V DC | 83.33 A | 3 AWG or larger |
| 24 V DC | 41.67 A | 6 AWG |
| 48 V DC | 20.83 A | 12 AWG |
| 230 V AC | 4.35 A | 14 AWG |
This is the fundamental reason off-grid and automotive systems moved to 24 V and 48 V: at 12 V, a modest 1 kW inverter pulls over 83 A, demanding thick, expensive cable and generating real heat at every connection. Double the system voltage and the current — and the required copper — halves. It is also why you should never extend 12 V runs casually: voltage drop and heating both scale with current, so low-voltage DC punishes undersized wire twice.
Understanding Power Factor
Power factor (PF) is the number that confuses most beginners, so it deserves a plain explanation. In a DC circuit, or an AC circuit powering a pure resistance like a heater, voltage and current rise and fall in perfect step — all the current does useful work, and PF equals 1. But motors, transformers, and fluorescent ballasts store energy in magnetic fields each cycle and return part of it to the supply. This creates reactive current that flows back and forth without doing work — yet the wires and breakers must still carry it.
Power factor is the ratio of useful (real) power to total (apparent) power, always between 0 and 1. A motor with PF 0.83 draws about 20% more current than its wattage alone suggests (1 ÷ 0.83 = 1.20). That extra current heats wires, loads breakers, and is exactly what the PF term in the AC formulas accounts for. Utilities even penalize large industrial customers for low power factor, because it forces the grid to carry current that earns no revenue.
For everyday conversions: heaters, kettles, toasters, and incandescent bulbs are PF 1 — ignore the PF field. Induction motors are typically 0.80–0.90 (check the nameplate “cos φ”). Modern LED drivers and computer power supplies with active power-factor correction sit at 0.90–0.99. When you genuinely do not know, 0.85 is a safe, slightly conservative estimate for motor loads.
Why Converting Watts to Amps Matters
Circuit loading. Every socket circuit and lighting circuit has an amp limit set by its breaker. Add up the watts of everything plugged in, convert to amps, and compare against the breaker rating. If a 16 A breaker feeds a circuit and your loads total 3.5 kW at 230 V (15.2 A), you are at 95% of capacity — one more appliance trips it.
Wire and breaker selection. Once you know the amps, you can pick the conductor and protective device. The workflow is: watts → amps → wire size → breaker size. Skipping the first step and guessing is how undersized wiring happens.
Generator and inverter sizing. Portable generators and solar inverters list maximum output in watts or kVA, but their outlets and breakers are amp-rated. A “3 kW” generator on 230 V delivers at most 13 A — knowing the conversion tells you whether it can start your well pump or run the workshop.
Motor nameplate checks. Motors list rated power in kW or watts, voltage, and cos φ. Converting watts to amps gives the full-load current you set on the overload relay — the single most important number in motor protection. See the motor current page for nameplate reading in detail.
Common Mistakes
- Forgetting power factor on motors. Using PF 1 for a motor load underestimates current by 15–25%. A 2.2 kW motor at 400 V is 3.83 A at PF 0.83 but would wrongly calculate as 3.18 A at PF 1.
- Mixing line and phase voltage. On three-phase, always use line-to-line voltage (400 V or 415 V, not 230 V) with the √3 formula. Using 230 V in the three-phase formula gives an answer √3 times too large.
- Assuming 1 watt = 1 amp. Watts and amps are only equal at exactly 1 volt — a condition that never occurs in practice. The two are related through voltage, always.
- Using watts where kVA is needed. Generator and transformer capacity is rated in kVA (apparent power). Converting watts alone and comparing against a kVA rating undersizes the equipment whenever power factor is below 1.
- Ignoring inrush current. The steady-state amps from this calculator are not the starting current. Motors draw 5–7× running current for a few seconds at startup — breakers must be motor-rated to survive it.