⚡ VoltEdge

kW to Amps Motor Calculator

Find a motor's full-load current — this version factors in efficiency, because a motor always draws more electrical power than it delivers at the shaft.

Calculator Input

LIVE  Live calculation — type and watch the result.

The rated shaft power from the motor nameplate.
Three-phase supply voltage: 400, 415 or 480 V are typical.
Nameplate value if listed; otherwise 0.85 is a fair estimate.
IE3 motors run ~90–94%. Older or small motors can be lower.

Full-Load Amps (FLA)

—
Enter values to calculate

Formula Used

—

Reading a Motor Nameplate

A motor’s nameplate is the small metal plate fixed to its frame, and it is the single most reliable source of the numbers this calculator needs. Nameplate figures always beat estimates, so learn to read yours before touching a single input field.

The plate usually carries these entries:

If the plate is damaged or a figure is missing, fall back to typical values: 0.85 for power factor and 90 percent efficiency are fair starting points for a standard induction motor.

How the Motor Calculator Works

1

Enter the motor’s kW rating

This is the mechanical power at the shaft, not the electrical input.

2

Enter voltage and power factor

Use the nameplate figures — they beat any estimate.

3

Enter the efficiency

Losses mean the motor draws extra current; efficiency accounts for it.

4

Read the full-load amps

The steady current the motor draws at rated output.

Motor FLA Formulas

Full-load amps: I = (kW × 1000) ÷ (√3 × V × PF × η)

The motor formula adds efficiency (η) to the standard three-phase equation, because part of the electrical input is lost as heat and friction before it reaches the shaft.

Reverse (amps → kW): kW = (I × √3 × V × PF × η) ÷ 1000

Rearrange to recover the shaft power from a measured current draw.

Horsepower note: 1 HP ≈ 0.746 kW

Nameplate in horsepower? Multiply by 0.746 to get kilowatts first.

Why Efficiency Belongs in the Formula

The kilowatt figure on a nameplate describes output power — what the shaft hands to the pump, fan, or gearbox. No motor converts electricity perfectly, so the electrical input must be larger than the mechanical output. Dividing by efficiency (as a decimal) corrects for that: a 7.5 kW motor running at 90 percent efficiency actually draws 7.5 ÷ 0.90 = 8.33 kW from the supply, and the current calculation must be based on that higher number.

The lost energy does not vanish — it leaves as heat in the windings, friction in the bearings, and eddy currents in the iron core. Skip the efficiency term and the answer comes out roughly 10 to 15 percent too low, which is exactly the margin you cannot afford when sizing cables and overload relays. For the same reason, older or rewound motors with degraded efficiency draw noticeably more current than their kilowatt rating would suggest.

Horsepower to Kilowatts

Motors are still sold in horsepower in many markets, and this calculator works in kilowatts, so the conversion matters. One mechanical horsepower equals 0.746 kilowatts — multiply the HP rating by 0.746 and you are done.

HorsepowerKilowatts
1 HP0.75 kW
2 HP1.49 kW
5 HP3.73 kW
7.5 HP5.59 kW
10 HP7.46 kW
15 HP11.19 kW
20 HP14.92 kW

Electrical and metric horsepower differ very slightly, but 0.746 kW per HP is the standard figure printed on motor nameplates and used in every conversion table you will meet.

Typical Full-Load Amps by Motor Size

Use this table as a quick reference when you only know the kilowatt rating. It assumes a 400 V three-phase supply, a power factor of 0.85, and 90 percent efficiency — realistic figures for a modern induction motor.

Motor sizeFull-load amps (A)
1 kW1.89 A
2 kW3.77 A
5 kW9.43 A
7.5 kW14.15 A
10 kW18.87 A
15 kW28.30 A

These are estimates, not ratings. Your nameplate FLA is the authority: if a motor of a given size lists a noticeably higher FLA, it probably runs at a lower efficiency or power factor than the assumptions above. Small fractional-kilowatt motors are also proportionally less efficient, so their real current can exceed the table.

Starting Current vs Running Current

The full-load amps figure describes the motor at steady speed under full load. Starting is a different animal: a motor at standstill looks almost like a short circuit to the supply, and direct-on-line starting can pull five to seven times the FLA for a few seconds. A 14.15 A motor may briefly demand close to 100 A before it spins up.

This is why motor protection is split into two jobs. The overload relay is tuned to the running current and trips on sustained overload, typically around 115 to 125 percent of FLA. The breaker or fuse — usually a motor-rated D-curve or magnetic-only device — must ride through the inrush without nuisance tripping while still clearing a genuine fault. Sizing a plain thermal breaker exactly at FLA is a classic error: it will trip every time the motor starts.

Where frequent or gentle starts matter, a soft starter or a variable-frequency drive ramps the voltage or frequency and cuts starting current dramatically, often to around two to three times FLA. That is kinder to the motor windings, the driven machine, and the supply feeding them.

Worked Examples

Compare your calculated FLA against the amps stamped on the motor nameplate — they should be close. A real motor that consistently draws well above its calculated FLA is likely overloaded, undervolted, or developing a fault.

Efficiency matters more than most people expect: a 7.5 kW motor at 400 V, PF 0.85 and 90% efficiency draws (7.5 × 1000) ÷ (1.732 × 400 × 0.85 × 0.90) = 14.15 A. Also note the service factor — a 1.15 SF motor may legally run 15% above its FLA for short periods.

Example 1 — 10 kW motor at 400 V

Power factor 0.85, efficiency 92 percent:

I = (10 × 1000) ÷ (1.732 × 400 × 0.85 × 0.92) = 18.46 A

Example 2 — 15 HP motor at 415 V

First convert the horsepower: 15 × 0.746 = 11.19 kW. With power factor 0.86 and efficiency 91 percent:

I = (11.19 × 1000) ÷ (1.732 × 415 × 0.86 × 0.91) = 19.89 A

Example 3 — working backwards from a clamp meter

A 400 V motor shows a steady 25 A, with power factor 0.85 and efficiency 90 percent:

kW = (25 × 1.732 × 400 × 0.85 × 0.90) ÷ 1000 = 13.25 kW

If the nameplate says 10 kW, the motor is delivering about a third more than its rating — a finding worth acting on, not ignoring.

Common Mistakes

Safety Note

Motor circuits live behind distribution panels, and mistakes there bite harder than a tripped domestic breaker. Only qualified people should open a panel, change overload settings, or rewire a star-delta starter, and lockout/tagout applies whenever a motor is being worked on. Treat the numbers on this page as a design aid: they inform the conversation with your electrician, they do not replace one.

Frequently Asked Questions

What is full-load amps (FLA)?
The current a motor draws while delivering its rated shaft power at rated voltage. It is the baseline for sizing contactors, overloads, and cables.
Why does the motor formula include efficiency?
A motor converts electrical energy to mechanical work with losses. To deliver 7.5 kW at the shaft, it must draw more than 7.5 kW electrically — efficiency tells you how much more.
How do I convert HP to kW for this calculator?
Multiply horsepower by 0.746. A 10 HP motor is about 7.46 kW.
My motor draws more than the calculated FLA. Why?
Common causes: mechanical overload, low supply voltage, a failing bearing, or incorrect wiring. Investigate before assuming the calculation is wrong.
Does starting current matter here?
Yes, but separately. Direct-on-line starting can pull 5–7× the FLA for a few seconds. This calculator gives running current; size breakers for the inrush too.
What is the √3 in the three-phase formula?
It comes from the geometry of three-phase power: the three voltage phases sit 120 degrees apart, and √3 (about 1.732) is the factor that relates line-to-line voltage to per-phase power in a balanced system.
Should my breaker match the FLA exactly?
No. Overload protection is set near the FLA (typically 115–125 percent), while the breaker must be sized to survive the five-to-seven-times starting inrush. A breaker set exactly at FLA will nuisance-trip on every start.