⚡ VoltEdge

What Size Breaker for Your kW Load?

Your 3 kW heater and your breaker rating are talking about two different things. Here's the translation.

Circuit breaker sizing infographic
Circuit breaker sizing infographic
125 percent continuous load rule infographic
125 percent continuous load rule infographic

The 3-Step Method

1) Convert kW to amps: single-phase I = kW×1000 ÷ (V×PF); three-phase I = kW×1000 ÷ (1.732×V×PF). 2) Multiply by 1.25 for continuous loads. 3) Round up to the next standard breaker size.

Quick Reference (230 V Single-Phase, PF 1)

LoadAmps×1.25Breaker
2 kW8.7 A10.9 A16 A
3 kW13.0 A16.3 A20 A
5 kW21.7 A27.2 A32 A
7 kW30.4 A38.0 A40 A
9 kW39.1 A48.9 A50 A

Quick Reference (400 V Three-Phase, PF 0.85)

LoadAmps×1.25Breaker
5 kW8.5 A10.6 A16 A
10 kW17.0 A21.2 A25 A
20 kW34.0 A42.5 A50 A
30 kW51.0 A63.7 A80 A

Remember

The breaker protects the wire — always confirm the cable is rated for the breaker size you select.

Continuous vs Non-Continuous Loads

Electrical codes treat loads differently based on duration. A continuous load runs for 3 hours or more — water heaters, lighting circuits, EV chargers. A non-continuous load is everything else: a kettle, a power drill, a microwave. The distinction matters because heat builds up in breakers and wires over time.

For continuous loads, size the breaker at 125% of the load current (equivalently, load the breaker to only 80%). A 5.5 kW water heater at 230 V draws 23.9 A; × 1.25 = 29.9 A, so you need a 32 A breaker. For a non-continuous load of the same current, the next standard size above 23.9 A — a 25 A breaker — is acceptable, though many electricians still apply the 125% rule for margin.

When in doubt, treat the load as continuous. The cost difference between a 25 A and 32 A breaker is trivial; the safety margin is not.

Standard Breaker Sizes You’ll Actually Find

Breakers come in standard ratings, and you always round up — never down. Common IEC sizes: 6, 10, 16, 20, 25, 32, 40, 50, 63, 80, 100, and 125 A. (North American panels use 15, 20, 30, 40, 50, 60 A, among others.) If your calculation says 27.2 A, the answer is a 32 A breaker — there is no 28 A breaker, and a 25 A would nuisance-trip.

Match the breaker to the wire, not just the load: the breaker’s job is protecting the cable. A 32 A breaker on cable rated for only 20 A is a fire hazard, no matter what the load calculation says. Always verify the cable’s current rating meets or exceeds the breaker rating.

Three-Phase Worked Example

An 18 kW three-phase load at 400 V, power factor 0.85: first convert to amps — I = 18,000 ÷ (1.732 × 400 × 0.85) = 30.6 A. For a continuous industrial load, apply the 125% rule: 30.6 × 1.25 = 38.2 A. The next standard size up is a 40 A three-pole breaker.

Note the “three-pole” part: three-phase loads need a breaker that disconnects all three phases together. A 40 A single-pole breaker is a completely different device — always specify three-pole (3P) for three-phase circuits.

Frequently Asked Questions

What size breaker do I need for 3 kW?
At 230 V single-phase: 3,000 ÷ 230 = 13 A; × 1.25 = 16.3 A → use a 20 A breaker. At 400 V three-phase (PF 0.85): 5.1 A → a 10 A three-pole breaker.
Can I use a bigger breaker than calculated?
Only if the cable is rated for it. The breaker protects the wire — upsizing the breaker without upsizing the cable creates a fire risk.
What is the 125% rule for breakers?
Continuous loads (3+ hours) must not exceed 80% of the breaker rating, so you size the breaker at 125% of the load current. A 20 A continuous load needs a 25 A breaker minimum.
Do I need a single-pole or three-pole breaker?
Single-phase circuits use single-pole (or double-pole); three-phase circuits need a three-pole breaker that disconnects all phases simultaneously.
Why does my breaker trip below its rating?
Breakers trip on heat buildup over time. A sustained load at 90%+ of rating, a hot environment, or a loose connection adding heat can all cause tripping below the nominal rating. Check for overload first, then connections.